5-51
5
* Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications.
Pulse Train I/O: H6
H5-07
RTS control
ON/OFF
Enables or disables RTS con-
trol.
0: Disabled (RTS is always
ON)
1: Enabled (RTS turns ON
only when sending)
0 or 1 1 No A A A A 42BH 6-83
RTS Con-
trol Sel
H5-10
Unit Selec-
tion for
MEMO-
BUS regis-
ter 0025H
Selects the unit used for
MEMOBUS register 0025H
(output voltage monitor)
0: 0.1 V units
1: 1 V units
0 or 1 0 No A A A A 436H -
MEMO-
BUS 0025H
Unit
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
H6-01
Pulse train
input func-
tion selec-
tion
Selects the pulse train input
function
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A A A 42CH
6-7
6-30
Pulse Input
Sel
H6-02
Pulse train
input scaling
Sets the number of pulses in
Hertz, that is equivalent to
100% of the input item
selected in H6-01.
1000 to
32000
1440
Hz
Yes A A A A 4 2D H
6-7
6-30
Pulse In
Scaling
H6-03
Pulse train
input gain
Sets the input level according
to 100% of the input item
selected in H6-01, when a
pulse train with the frequency
set in H6-02 is input.
0.0 to
1000.0
100.0% Yes A A A A 42EH 6-30
Pulse Input
Gain
H6-04
Pulse train
input bias
Sets the input level according
to 100% of the input item
selected in H6-01, when the
pulse train frequency is 0.
-100.0
to
100.0
0.0% Yes A A A A 42FH 6-30
Pulse Input
Bias
H6-05
Pulse train
input filter
time
Sets the pulse train input delay
filter time constant in seconds.
0.00 to
2.00
0.10
s
Yes A A A A 4 30 H 6-30
Pulse In
Filter
H6-06
Pulse train
monitor
selection
Select the pulse train monitor
output items (value of the 
part of U1-).
There are two types of moni-
tor items: Speed-related items
and PID-related items.
1, 2, 5,
20, 24,
36
2 Yes A A A A 431H 6-81
Pulse Moni
Sel
H6-07
Pulse Moni
Scaling
Sets the number of pulses out-
put in hertz when the monitor
item is 100%.
Sets H6-06 to 2, and H6-07 to
0, to make the pulse train
monitor output synchronously
to the output frequency.
0 to
32000
1440
Hz
Yes A A A A 4 32 H 6-81
PO Scaling
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector