6-152
6
Selecting the Digital Reference
The setting range of the digital references is determined by the combination of the settings of o1-03 and F3-01.
The information monitored in U1-01 (Frequency reference) will also change.
DI-16H2 Reference Setting Ranges
With the DI-16H2 option card setting ranges can be set like shown in table below.
DI-08 Reference Setting Ranges
With the DI-16H2 option card setting ranges can be set like shown in the table below.
o1-03 F3-01
Switch
S1
Reference Input Mode
Reference Setting
Range
U1-01 Monitor Unit
o1-03 = 0 o1-03 = 1
0 or 1
0
12 bits 3-digit BCD with sign, 1% -110 to 110%
0.01 Hz 0.01%
16 bits 4-digit BCD with sign, 1% -110 to 110%
1
12 bits 3-digit BCD with sign, 0.1% -110.0 to 110.0%
16 bits 4-digit BCD with sign, 0.1% -110.0 to 110.0%
2
12 bits 3-digit BCD with sign, 0.01% -15.99 to 15.99%
16 bits 4-digit BCD with sign, 0.01% -110.0 to 110.0%
3
12 bits 3-digit BCD with sign, 1 Hz -400 to 400 Hz
16 bits 4-digit BCD with sign, 1 Hz -400 to 400 Hz
4
12 bits 3-digit BCD with sign, 0.1 Hz -159.9 to 159.9 Hz
16 bits 4-digit BCD with sign, 0.1 Hz -400.0 to 400.0 Hz
5
12 bits 3-digit BCD with sign, 0.01 Hz -15.99 to 15.99 Hz
16 bits 4-digit BCD with sign, 0.01 Hz -159.99 to 159.99 Hz
6 16 bits 5-digit BCD without sign, 0.01 Hz 000.00 to 399.98 Hz
7
12 bits 12-bit binary with sign, 100%/4095 -4095 to 4095
16 bits 16-bit binary with sign, 100%/30000 -33000 to 33000
2 to 39 -
12 bits 3-digit BCD with sign, 1 rpm -1599 to 1599 rpm 1 rpm
16 bits 4-digit BCD with sign, 1 rpm -15999 to 15999 rpm 1 rpm
40 to
39999
- 12 bits
3-digit BCD with sign, 100%/(1- to 4-digit setting
of o1-03)
-4095 to 4095
5th digit of o1-03 setting:
X = 0, unit: 1
X = 1, unit: 0.1
X = 2, unit: 0.01
X = 3, unit: 0.001
- 16 bits
4-digit BCD with sign, 100%/(1- to 4-digit setting
of o1-03)
-10999 to 10999
(when o1-03 = 9999)
10000
x = 1
to 3
- 16 bits
4-digit BCD with sign, 100%/10000 -11000 to 11000
F3-01 Reference Input Mode Reference Setting Range
U1-01 Monitor Unit
o1-03 = 0 o1-03 = 1
0 2-digit BCD with sign, 1% -110 to 110%
0.01 Hz 0.01%
1 2-digit BCD with sign, 0.1% -15.9 to 15.9%
2 2-digit BCD with sign, 0.01% -1.59 to 1.59%
3 2-digit BCD with sign, 1 Hz -159 to 159 Hz
4 2-digit BCD with sign, 0.1 Hz -15.9 to 15.9 Hz
5 2-digit BCD with sign, 0.01 Hz -1.59 to 1.59 Hz
6-
7
12-bit binary with sign, 100%/
4095
-255 to 255

Table of Contents

Other manuals for Omron VARISPEED F7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED F7 and is the answer not in the manual?

Omron VARISPEED F7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED F7
CategoryInverter
LanguageEnglish

Related product manuals