Parameter Reference 15-1
AC10 Inverter
Chapter 15 Parameter Reference
Basic parameters: F100-F160
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F100
User’s Password
09999
F102
Inverter’s Rated Current (A)
Subject to
inverter model
*
F103
Inverter Power (kW)
Subject to
inverter model
*
F104
Reserved
F105
Software Edition No.
Subject to
inverter model
F106
Control Mode
Setting range:
0:Sensorless vector control
(SVC);
1: Reserved;
2: V/HZ
3: Vector control 1
6: PMSM sensorless vector
control
2
F107
Password Protection
0: Disabled;
1: Enabled
0
F108
User’s Password
09999
8
F109
Starting Frequency (Hz)
0.010.00Hz
0.0
F110
Holding Time of Starting Frequency (s)
0.0999.9
0.0
F111
Max Frequency (Hz)
F113590.0Hz
50.00
F112
Min Frequency (Hz)
0.00HzF113
0.50
F113
Target Frequency (Hz)
F112F111
50.00
F114
1
st
Acceleration Time (s)
0.13000
subject to
inverter
model
F115
1
st
Deceleration Time (s)
0.13000
F116
2
nd
Acceleration Time (s)
0.13000
F117
2
nd
Deceleration Time (s)
0.13000
F118
Base Frequency (Hz)
15.00590.0
50.00
F119
Setting Accel/Decel Reference Time
0: 0~50.00Hz
1: 0~ F111
0
F120
Forward/Reverse Switchover Dead-Time
0.03000
0.0
F121
Reserved
F122
Reverse Running Forbidden
0: False;
1: True
0
F123
Minus Frequency is Valid in the Mode of Combined
Speed Control.
0False
1Trued
0
F124
Jogging Frequency
F112F111
5.00Hz

Table of Contents