15-4 Parameter Reference
AC10 Inverter
Running control mode: F200-F230
Function
Code
Function Definition
Setting Range
Mfr’s Value
Change
F200
Source of start command
0: Keypad command
1: Terminal command
2: KeypadTerminal
3:MODBUS
4: KeypadTerminalMODBUS
4
F201
Source of stop command
0: Keypad command
1: Terminal command
2: KeypadTerminal
3:MODBUS
4: KeypadTerminalMODBUS
4
F202
Mode of direction setting
0: Forward running locking
1: Reverse running locking
2: Terminal setting
3: Keypad
0
F203
Main frequency source (X)
0: Digital setting memory
1: External analog AI1
2: External analog AI2
3: Reserved
4: Stage speed control
5: No memory by digital setting
6: Reserved
7: Reserved
8: Reserved
9: PID adjusting
10: MODBUS
0
F204
Secondary frequency source (Y)
0: Digital setting memory
1: External analog AI1
2: External analog AI2
3: Reserved
4: Stage speed control
5: PID adjusting
6: Reserved
0
F205
Reference for selecting secondary frequency
source (Y) range
0: Relative to max frequency
1: Relative to main frequency (X)
0
F206
Secondary frequency (Y) range
0100
100
F207
Frequency source selecting
0: X
1: X+Y
2: X or Y (terminal switchover)
3: X or X+Y (terminal switchover)
4: Combination of stage speed and
analog
5: X-Y
6: Reserved
0