Parameter Reference 15-5
AC10 Inverter
Function
Code
Function Definition
Setting Range
Mfr’s Value
Change
F208
Terminal operation mode
0: No function
1: Two-line operation mode 1
2: Two-line operation mode 2
3: Three-line operation mode 1
4: Three-line operation mode 2
5: Start/stop controlled by direction
pulse
0
F209
Motor stopping mode
0: stop by deceleration time
1: free stop (coast stop)
0
F210
Frequency display accuracy
0.012.00
0.01
F211
Speed of digital control
0.01100.00Hz/S
5.00
F212
Direction memory
0: Disabled
1: Enabled
0
F213
Auto-starting after repowered on
0: Disabled
1: Enabled
0
F214
Auto-starting after reset
0: Disabled
1: Enabled
0
F215
Auto-starting delay time
0.13000.0
60.0
F216
Auto-start restart attempts
05
0
F217
Fault reset delay
0.010.0
3.0
F218
Reserved
F219
Write EEPROM by Modbus
0: Disabled
1: Enabled
1
F220
Frequency memory after power-down
0: Disabled
1: Enabled
0
F221-
F223
Reserved
F224
When target frequency is lower than Min
frequency
0: Stop
1: run at min frequency
1
F225-
F227
Reserved
F228
Application selection
0: None
1: Basic speed control
2: Auto/manual control
3: Stage speed control
4: Terminal control
5: PID control
0
No Macro
selected
F229~
F230
Reserved