EasyManua.ls Logo

Parker 10G-46-0600-BF

Parker 10G-46-0600-BF
151 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation and Simple Running 8-8
AC10 Inverter
+
-
S1
V
J
J5
ii. Press the “M” key, to enter the programming menu.
iii. Study the parameters of the motor: the operation process is the same as that of
example 1. (Refer to 8.3.1 for tuning of the motor).
iv. Set functional parameters of the inverter:
Frames 1 5 upto 22kW
v. There is a red two-digit coding switch SW1 near the control terminal block, as
shown in Figure 8-4. The function of coding switch is to select the voltage signal
(05V/010V) or current signal of analog input terminal AI2, current channel is
default. In actual application, select the analog input channel through F203. Turn
switches 1 to ON and 2 to ON as illustrated in the figure, to select 020mA
current speed control.Other states and modes of these switches are shown in
table 8-2,
Frames 6 11 30kW 150kW
vi. There is a red four-digit coding switch SW1 near the control terminal blockr, as
shown in Figure 8-5. The function of coding switch is to select the input range (0
5V/010V/0~20mA) of analog input terminal AI1 and AI2. In actual application,
select the analog input channel through F203. AI1 channel default value is 0~10V,
AI2 channel default value is 0~20mA. Other states and modes of these switches
are shown in table 8-3.
vii. There is a toggle switch S1 at the side of control terminals,refer to Fig 8-6. S1 is
used to select the voltage input range of AI1 channel. When turning S1 to “+”, the
input range is 0~10V, when turning S1 to “-”, the input range is -10~10V.
viii. Close the switch DI3, the motor starts forward running;
ix. The potentiometer can be adjusted and set during running, and the current setting
frequency of the inverter can be changed;
x. During running process, switch off the switch DI3, then, close DI4, the running
direction of the motor will be changed;
xi. Switch off the switches DI3 and DI4, the motor will decelerate until it stops running;
xii. Switch off the main switch to power off the inverter.
xiii. Analog output terminal AO1 can output voltage and current signal, the selecting
switch is J5, refer to Fig 8-7 the output relation is shown in Table 8-.4.
Figure 8-4 Figure 8-5 Figure 8-6 Figure 8-7
Function code
Parameter
Values
F203
Main frequency source
1
F208
Terminal operational mode
1
ON
2
1
SW1
SW1
ON
1
4
2
3

Table of Contents

Related product manuals