9-16 Function Parameters
AC10 Inverter
F216 Auto-start restart attempts
F216 sets the most times of auto-starting in case of repeated faults. If starting times are more
than the setting value of this function code, inverter will not reset or start automatically after
fault. Inverter will run after running command is given to inverter manually.
F217 sets delay time for fault reset. The range is from 0.0 to 10.0s which is time interval from
fault to resetting.
F219 Write EEPROM by Modbus
F220 Frequency memory after power-down
F220 sets whether or not frequency remember after power-down is valid.
This function is valid for F213 and F214. Whether or not to memory running state after power-
down or malfunction is set by this function.
The function of frequency memory after power-down is valid for main frequency and secondary
frequency that is given by digital. Because the digital given secondary frequency has positive
polarity and negative polarity, it is saved in the function codes F155 and F156.
Table 9-1 Combination of Speed Control
0. Memory of
digital setting
4 Terminal stage
speed control
●: Inter-combination is allowable.
〇: Combination is not allowable.
The mode of automatic cycle speed control is unable to combine with other modes. If the
combination includes the mode of automatic cycle speed control, only main speed control
mode will be valid.
F224=1, when target frequency is lower than Min frequency, inverter will run at Min frequency.
F224 when target frequency is lower than
Min frequency
0: stop
1: run at min frequency