Function Parameters 9-15
AC10 Inverter
F210 Frequency display
accuracy
Under keypad speed control or terminal UP/DOWN speed control, frequency display accuracy
is set by this function code and the range is from 0.01 to 2.00. For example, when F210=0.5,
▲/▼terminal is pressed at one time, frequency will increase or decrease by 0.5Hz.
F211 Speed of digital control
When UP/DOWN terminal is pressed, frequency will change at the setting rate. The Mfr’s
value is 5.00Hz/s.
This function is valid when three-line operation mode 1(F208=3) is valid.
When F212=0,after inverter is stopped, reset and repowered on, the running direction is not
memorized.
When F212=1,after inverter is stopped, reset and repowered on, if inverter starts running but
no direction signal, inverter will run according the memory direction.
F213 Auto-starting after
repowered on
F214 Auto-starting after reset
Whether or not to start automatically after repowered on is set by F213
F213=1, Auto-starting after repowered on is valid. When inverter is power off and then
powered on again, it will run automatically after the time set by F215 and according to the
running mode before power-down. If F220=0 frequency memory after power-down is not valid,
inverter will run by the setting value of F113.
F213=0, after repower-on, inverter will not run automatically unless running command is given
to inverter.
Whether or not to start automatically after fault resetting is set by F214
When F214=1, if fault occurs, inverter will reset automatically after delay time for fault reset
(F217). After resetting, inverter will run automatically after the auto-starting delay time (F215).
If frequency memory after power-down (F220) is valid, inverter will run at the speed before
power-down. Otherwise, inverter will run at the speed set by F113.
In case of fault under running status, inverter will reset automatically and auto-start. In case of
fault under stopped status, the inverter will only reset automatically.
When F214=0, after fault occurs, inverter will display fault code, it must be reset manually.
F215 Auto-starting delay time
F215 is the auto-starting delay time for F213 and F214. The range is from 0.1s to 3000.0s.