Function Parameters 9-23
AC10 Inverter
Figure 9-6 PTC Heat Protection
When the coding switch is in the end of “NPN”, PTC resistor should be connected between CM
and DIx terminal. When the coding switch is in the end of “PNP”, PTC resistor should be
connected between DIx and 24V. The recommended resistor value is 16.5KΩ.
Because the accuracy of external PTC has some differences with manufacture variation some
errors can exist, thermistor protection relay is recommended.
NOTE: To use this function double insulate motor thermistor must be used.
Table 9-4 Accel/decel selection
Accel/decel
switchover 2 (34)
Accel/decel
switchover 1 (18)
Present accel/decel time
Related
parameters
0
0
The first accel/decel time
F114, F115
0
1
The second accel/decel time
F116, F117
1
0
The third accel/decel time
F277, F278
1
1
The fourth accel/decel time
F279, F280
Table 9-5 Instructions for multistage speed
K4
K3
K2
K1
Frequency setting
Parameters
0
0
0
0
Multi-stage speed 1
F504/F519/F534/F549/F557/F565
0
0
0
1
Multi-stage speed 2
F505/F520/F535/F550/F558/F566
0
0
1
0
Multi-stage speed 3
F506/F521/F536/F551/F559/F567
0
0
1
1
Multi-stage speed 4
F507/F522/F537/F552/F560/F568
0
1
0
0
Multi-stage speed 5
F508/F523/F538/F553/F561/F569
0
1
0
1
Multi-stage speed 6
F509/F524/F539/F554/F562/F570
0
1
1
0
Multi-stage speed 7
F510/F525/F540/F555/F563/F571
0
1
1
1
Multi-stage speed 8
F511/F526/F541/F556/F564/F572
1
0
0
0
Multi-stage speed 9
F512/F527/F542/F573
1
0
0
1
Multi-stage speed 10
F513/F528/F543/F574
1
0
1
0
Multi-stage speed 11
F514/F529/F544/F575
1
0
1
1
Multi-stage speed 12
F515/F530/F545/F576
1
1
0
0
Multi-stage speed 13
F516/F531/F546/F577
1
1
0
1
Multi-stage speed 14
F517/F532/F547/F578
1
1
1
0
Multi-stage speed 15
F518/F533/F548/F579