9-46 Function Parameters
AC10 Inverter
FA58 Fire pressure given value (%)
FA58 is also called second pressure, when the fire pressure switchover terminal is valid,
pressure target value will switch into second pressure value.
0: Disabled
1: Emergency fire mode 1
2: Emergency fire mode 2
When emergency fire mode is valid and emergency fire control terminal is valid, fire mode
controls are valid and inverter will run at the frequency of FA60 or target frequency until
inverter is broken. When OC and OE protection occur, inverter will reset automatically and
start running .
Emergency fire mode 1: when the terminal is valid, inverter will run at target frequency.
Emergency fire mode 2: when the terminal is valid, inverter will run at the frequency of FA60.
FA60 Running frequency of emergency fire
When the emergency fire mode 2 is valid and the emergency fire control terminal is valid,
inverter will run at the frequency set by FA60.
FA62 when emergency fire
control terminal is invalid
0: inverter can not be stopped manually
1: inverter can be stopped manually
•FA62=0, when emergency fire control terminal (DIx=33) is invalid, before repower or inverter,
or reset inverter, inverter can not be stopped manually.
•FA62=1, when emergency fire control terminal (DIx=33) is invalid, after quitting from
emergency fire mode, inverter can be stopped manually