192-011006N8 PSD1 Installation Guide
192-011006N8 2019-07 09.10.19 09:27 19 (109)
Data of the integrated dynamic brake module PSD1-M_P
Mains module
Max. Duty Cycle
value
PSD1-M_P010 28.8 A
27 Ω
PSD1-M_P020 78.0 A
10 Ω
• Suitable for use on a circuit capable of delivering not more than 5000 rms
Symmetrical Amperes, 480 V ac +10 % maximum, when protected by Listed
♦ DIVQ Circuit Breakers manufactured by ABB, Stotz-Kontakt GmbH, Mod. No. S203UP-K
/ 480 Vac, 25 A for PSD1-M_P010
or
♦ R/C (JFHR2/8) Semiconductor Fuse type manufactured by Cooper Bussmann LLC,
Mod. No. 170M1366 oder 170M1566D, 690 VAC, 80 A, 200 kA RMS Sym for
PSD1-M_P020..
• Power supply units PSD1-M_P need a fusing on the main site (branch circuit
protection) as stated below.
PSD1-M_P010
device
Measure for line and device protection:
UL listing (DIVQ) fuses
Manufacturer: ABB, Stotz-Kontakt GmbH (E212323)
Model No.: S203UP-K, 1 fuse
480 VAC, 3-phase, 25 A, operating temperature 55 °C
PSD1-M_P020
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC (depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
Tightening torque of the wiring terminals
Risk of Electric Shock, wait at least 10 minutes before removing cover.
The field wiring terminals should be tightened with the torques mentioned below.
Only the supplied mating connectors must be used.
2
2
0.22 ... 0.25 Nm
1.95 ... 2.21 Lb.in
2
1.1 ... 1.7 Nm
11 ... 15 Lb.in
2