192-011006N8 PSD1 Installation Guide
192-011006N8 2019-07 09.10.19 09:27 97 (109)
8.2.3. Mains Connection Power module PSD1-M_P020 without line choke
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC (depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
8.2.4. Mains connection Power module PSD1-M_P020 with line choke
Increased power by means of a line choke (see page
87
)
PSD1-M_P020 with line
choke
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC (depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
Current on the mains PE (see page 24) (>3,5 mA)
Possible supply networks (see page 24): TN
The specified performance data are only valid in connection with line choke (see
page 87) IND-0002-01 or IND-0002-02 (UL).