192-011006N8 PSD1 Installation Guide
192-011006N8 2019-07 09.10.19 09:27 39 (109)
S12: Device address high order half-byte (accept with power ON)
S13: Device address low value half-byte (accept with power ON)
Example: S12=2, S13=1
Address= 0x21: S12*16 + S13 = 33
Addressing 1 ... 240 (0xF0) possible; Values 241 ... 255 reserved!
After switching on PSD, the IP address is set to the value "192.168.100.S12_S13".
If the IP address has been changed and is not longer known, it can be reset with
S12_S13 = 253 (0xF9) to:
IP address = 192.168.10.2
SubNetmask = 255.255.0.0
Gateway_IP = 192.168.10.254
Host name = PSD1-002
The complete IP address can be redefined via the objects 0x2605.5 & 0x2605.01 .
Addresses 0 and 241 ... 255 are not possible.
Connection is configured in PSD ServoManager.
4.11 Communication interfaces
In this chapter you can read about:
X61, X62 Ethernet Connection ................................................................................................. 66
4.11.1. X61, X62 Ethernet Connection
RJ45-Socket: Assignment
Pin
Wire pair
No.
RJ45 (X61)
RJ45 (X62)
out
in
1
2
Tx +
Tx +
2
2
Tx -
Tx -
3
3
Rx +
Rx +
4
1
-
factory use
5
1
-
factory use
6
3
Rx -
Rx -
7
4
-
factory use
8
4
-
factory use
Wiring with Ethernet Crossover cable Cat5e (from X61 to X62 of the next device
without termination); for this, we offer our CBD000C0-T00-T0 (see page 93)
interface cable.
Please use shielded cables:
SF/UTP: Cable shielded in total or
S / STP, S / FTP: additional shielding around the 4 wire pairs.
Place the shield flat on the plug!