30 HUNTER-PRO Series Installation Guide
3.5.1.2 Settings for the AC siren
In “General Parameters”, set “D” to “-”. This will set the siren to AC (see section 5.7.1).
Set JP5, JP10 & JP6 to short pins 2 & 3.
Figure 26. Connecting AC Siren
3.5.2 DC Siren
Connect the siren between the Ext. or Int. terminals and “-”.In “General Parameters”
screen, set “+” under “D” (see section 5.7.1). This will set the siren as DC.
Set JP5 & JP10 to short pins 2 & 3 and JP6 to short pins 1 & 2.
Figure 27. 2 DC/Bell siren wirings
When using a DC siren, it is recommended to connect a 1kΩ EOL
resistor to eliminate noises
The following table describes the various siren installation possibilities: