EasyManua.ls Logo

Polhemus VIPER 4 - Configuring Viper Multi - Source Modes of Operation; Single - Source Mode; Dual Source Mode; Local - Source Mode

Polhemus VIPER 4
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USER MANUAL
URM18PH392 Rev A. May 2020 Page 31 of 86
3.5 CONFIGURING VIPER MULTI-SOURCE MODES OF OPERATION
As described previously in Section 2. , VIPER™ is able to drive up to four Source components.
Note: When multiple Sources are used, each Source must operate at a
different electromagnetic (EM) frequency.
If multiple Sources of the same frequency are connected, VIPER™ will not
operate.
Polhemus offers Sources in a variety of EM frequencies.
When VIPER™ powers up, it detects plugged in Sensor and Source components. (Hot swapped Sensors are also
detected when plugged in while VIPER is running.)
Depending on the pattern of connected Sources, VIPER™ defaults to one of several standard modes of operation.
These modes are detailed in the following Sections 3.5.1, 3.5.2, and 3.5.3.
Each mode is characterized by:
Which Source(s) the Sensor detects for determining position and orientation (P&O)
and
Which Source is the referenced Cartesian origin (0, 0, 0) and null orientation.
SINGLE-SOURCE MODE 3.5.1
Applies to VIPER8 and VIPER™ 16 systems.
One Source is plugged into Source port 1.
All Sensors report P&O relative to Source 1.
No Source is plugged into any other Source port.
DUAL-SOURCE MODE 3.5.2
Each group of 8 Sensors report P&O with respect to Sources 1 and 3. In this mode, VIPER™ behaves as two
independent 8-Sensor tracking systems.
Applies to VIPER™ 16 systems only.
Two Sources are plugged into Source ports 1 and 3.
Sensors 1-8 report P&O relative to Source 1.
Sensors 9-16 report P&O relative to Source 3.
Sources 1 and 3 must operate at different EM frequencies*.
No Source is plugged into Source ports 2 and 4.
*See warning note above.
LOCAL-SOURCE MODE 3.5.3
Each group of 4 Sensors report P&O with respect to the Local Source. Refer to Figure 15 and Figure 16 below to
see the location of Local Sources.
Applies to all VIPER™ systems; this is the standard operating mode for VIPER™ 4.
On a VIPER 8 system:
Behaves as two independent 4-Sensor systems.
Two Sources are plugged in to Source ports 1 and 2.
Sources 1 and 2 must operate at different EM frequencies*.
Sensors 1-4 report P&O with respect to their Local Source: Source 1.
Sensors 5-8 report P&O with respect to their Local Source: Source 2.
FIGURE 13. VIPER™ 16 SINGLE-SOURCE MODE
FIGURE 14. VIPER™ 16 DUAL-SOURCE MODE
FIGURE 15. VIPER™ 8 LOCAL SOURCE LOCATIONS

Table of Contents