Powered by Safety
®
9
Equipment Description
01.4IB.48041
Table B System Specifications (cont.)
Characteristic Minimum Typical Maximum Units Comments
Operating Environmental Conditions
Temperature -30 (-22) 70 (158) C (F) IEC 60068-2-14
Note: LCD viewing angle is reduced when ambient temperatures are below -20 C
Humidity 5 95 %RH Non-condensing
IP Rating (Mounted) 54 IEC 60529:2009
Vibration Class 1 IEC 60255-21-1
Shock Class 1 IEC 60255-21-2
Pollution Degree 2
Overvoltage Category II
Altitude 2000
MASL
(meters above
sea level)
Atmospheric Pressure 80 110
kPa
(kilopascal)
Storage Environmental Conditions
Temperature -40 (-40) 85 (185) C (F)
Humidity 5 95 %RH
Vibration Class 1 IEC 60255-21-1
Shock Class 1 IEC 60255-21-2
Bump Class 1 IEC 60255-21-3
Standard Probe Specications (BSL007, BSL010, BSL015)
Material Nylon
Minimum Bend Radius 12 (0.5) mm (in)
Length 7, 10, 15, (21, 30, 45) m (ft)
Operating Temperature -40 (-40) 120 (248) C (F)
High Voltage Characteristics 38kV, over 8” gap
High Temperature Probe Specications (BSPN/AHT)
Material Fluoropolymer
Minimum Bend Radius 12 (0.5) mm (in)
Length Detachable probe, 0.25m (10”). Max ber extension 10m (30’)
Operating Temperature -40 (-40) 160 (320) C (F)
High Voltage Characteristics 38kV, over 8” gap
Probe Mounting Fixture Specications
Material Tin plated copper
Manufacturer Tyco/Amp
Approvals UL/CSA
Part Numbers
¼” Hardware Tyco/Amp PN 33465
/” Hardware Tyco/Amp PN 36807
½” Hardware Tyco/Amp PN 36808