Figure 45 Alarm Configuration Web Page
By default, the BriteSpot®
Plus comes with alarm one
preconfigured. See Table K Alarm
Configuration Web Page Settings for
all default values.
Table K Alarm Configuration Web Page Settings
Parameter
Default Value
Range/Options
Alm 1 Alm 2-8
Type
Abs
Temp
Disabled
Disabled, Absolute
Temperature,
Absolute Current
Warning O 85 °C 1 Any integer (°C or °F or A)
Note: Warning O is the threshold for a warning condition to end.
Warning On 90 °C 2 Any integer (°C or °F or A)
Note: Warning On is the threshold for a warning condition to begin.
This parameter must be greater than the value that Warning O
is set to.
Alarm O 100 °C 3 Any integer (°C or °F or A)
Note: Alarm O is the threshold for a warning condition to end.
This parameter must be greater than the value that Warning O
is set to.
Alarm On 105 °C 4 Any integer (°C or °F or A)
Note: Alarm On is the threshold for a alarm condition to begin.
This parameter must be greater than both the value that Warning
On is set to as well as the value that Alarm O is set to.
Latching False False True/False
Sources
All
available
BriteSpot
sources
None
BriteSpot Channels 1-36
(when available)
MCS 1-8 (when available)