POWER WIRING INSTALLATION NOTES
D
D
NOTE:
Callout letter
and
map to drawing #164201300---6
,,,
A---9
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table L. Ratings & External Wiring Requirements for
Po werwar e 9330 (25 kVA---40 kV A)
Options Cabinet OUTPUT Transformer
Ratings 50/60 Hz
Basic unit ratings at Voltage
Conductor
0.7 lagging PF load
Series/
Model
kVA/KW
Input Output
u
pu
Current
(Amps)
Minimum
Size
40/25 23.8/16.6 208/220 208 66 4
40/25 23.8/16.6 208/220 480 28.6 10
COut
ut from
40/30 28.5/20 208/220 208 79 3
AC
Output Transformer
40/30 28.5/20 208/220 480 34.3 8
OUTPUT
to Critical Load
0.95min.PF
40/35 33.2/23.3 208/220 208 92.4 2
.
.
3, 1 Neutral, 1 gnd
40/35 33.2/23.3 208/220 480 40 8
40/40 38/26.6 208/220 208 105.5 1
40/40 38/26.6 208/220 480 45.7 6
Table M. Ratings & External Wiring Requirements for
Po werwar e 9330 (25 kVA---40 kV A)
Options Cabinet OUTPUT Without Output Transformer
Ratings 50/60 Hz
Basic unit ratings at Voltage
Conductor
0.7 lagging PF load
Series/
Model
kVA/KW
Input Output
u
pu
Current
(Amps)
Minimum
Size
40/25 25/17.5 208/220 208/220 69.4 4
AC
C Output fro m Output
to Critical Load
40/30 30/21 208/220 208/220 83 2
OUTPUT
(0.95min.PF)
40/35 35/24.5 208/220 208/220 97 1
3, 1 Neutral, 1 gnd
40/40 40/28 208/220 208/220 111 1/0