DESCRIPTION:
DATE:
DRAWING NO:
10 of 17
SHEET:
REVI SION:
N
013004
NOTE: Customer ground, size 1/0, can
be run in any conduit listed in
Tab l e s T a n d U.
POWER WIRING INSTALLATION NOTES
164201300---1
A --- 1 1
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table O. UPS Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)
Terminal Function Te rm i na l Function
Size of Pressure
Termination
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
E6 Phase A 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
Rectifier and Bypass
E7 Phase B 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
ng
e
nput
E8 Phase C 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
E12 Neutral 1 --- # 6 --- 3 5 0 k c m i l
31 (275)
5/16 in. Hex
AC Input to UPS
E1 Phase A 1 --- # 8 --- 2 / 0 13 (110) 3/16 in. Hex
Rectifier
E2 Phase B 1 --- # 8 --- 2 / 0 13 (110) 3/16 in. Hex
ua
nput
E3 Phase C 1 --- # 8 --- 2 / 0 13 (110) 3/16 in. Hex
AC Input To Bypass
E6 Phase A 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
(Dual Input)
E7 Phase B 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
E8 Phase C 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 in. Hex
E12 Neutral 1 --- # 6 --- 3 5 0 k c m i l
31 (275)
5/16 in. Hex
Single Feed Jumper
— Phase A N/A 6 (50) 1/4–20 Stud
on Bypass Input
— Phase B N/A 6 (50) 1/4–20 Stud
erm
na
oc
— Phase C N/A 6 (50) 1/4–20 Stud
AC Output to Critical
E9 Phase A 1 --- # 8 --- 2 / 0
13 (110)
3/16 in. Hex
Load
E10 Phase B 1 --- # 8 --- 2 / 0
13 (110)
3/16 in. Hex
E11 Phase C 1 --- # 8 --- 2 / 0
13 (110)
3/16 in. Hex
E12 Neutral 1 --- # 6 --- 3 5 0 k c m i l
31 (275)
5/16 in. Hex
DC Input from
Battery to UPS
N/A
Battery
(+)
Red Battery
Connector
N/A N/A
N/A
Battery
( --- )
Black Battery
Connector
N/A N/A
External Battery
E4 Positive 1 --- # 8 --- 2 / 0
13 (110)
3/16 in. Hex
Input to UPS
E5 Negative 1 --- # 8 --- 2 / 0
13 (110)
3/16 in. Hex
Customer Ground Ground Ground 2 --- # 1 4 --- 1 / 0 5.6 (50) Slotted