NOTE: Customer ground, size 1/0, can
be run in any conduit listed in
Tab le s R t h rou g h U .
POWER WIRING INSTALLATION NOTES
164201300---1
A --- 1 2
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table P. Options Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)
Terminal Function Te rm i na l Function
Size of Pressure
Termination
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
L1 Phase A 1 --- # 1 4 --- # 2
#2 --- 5.6 (50)
Rectifier Transformer
L2 Phase B 1 --- # 1 4 --- # 2
#4---#6 --- 5.0 (45)
---
Slotted
1
L3 Phase C 1 --- # 1 4 --- # 2
---
.
# 1 0 --- # 1 4 --- 4 . 0 ( 3 5 )
AC Input To UPS
L1 Phase A 1 --- # 1 4 --- # 2
y
(TB1)
L2 Phase B 1 --- # 1 4 --- # 2
#2 --- 5.6 (50)
# 4 --- # 6 --- 5 . 0
45
L3 Phase C 1 --- # 1 4 --- # 2
.
#8 --- 4.5 (40)
---
---
otte
N Neutral 1 --- # 1 4 --- # 2
---
---
.
AC Output from
X1 Phase A 1 --- # 1 4 --- 2 / 0
2.5-2.9(22-26)
3/16 in. Hex
u
u
to Critical Load
X2 Phase B 1 --- # 1 4 --- 2 / 0
2.5-2.9(22-26)
3/16 in. Hex
(TB1)
X3 Phase C 1 --- # 1 4 --- 2 / 0
2.5-2.9(22-26)
3/16 in. Hex
N Neutral 3 --- # 1 4 --- 2 / 0
2.5-2.9(22-26)
3/16 in. Hex
Customer Ground Ground Ground 2 --- # 1 4 --- 1 / 0 5.6 (50) Slotted
Table Q. Options Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)
Terminal Function Te rm i na l Function
Size of Pressure
Termination
Vendor
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
L1 Phase A 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
Rectifier Transformer
L2 Phase B 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
(TB1)
L3 Phase C 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
AC Input To UPS
L1 Phase A 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
Bypass Transformer
TB1
L2 Phase B 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
Ll3 Phase C 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- # 4 --- 4 / 0
Entrelec 3.2-3.7(28-33)
6mm
Allen
AC Output from
X1 Phase A 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
Output T ransformer
to Critical Load
X2 Phase B 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
(TB1)
X3 Phase C 1 --- # 1 4 --- 1 / 0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- # 4 --- 4 / 0
Entrelec 4-6(35-52)
6mm
Allen
Customer Ground Ground Ground 2 --- # 1 4 --- 1 / 0 N/A 5.6 (50) Slotted