DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVI SION:
G
1of5
051502
CUSTOMER INTERFACE WIRING
INSTALLATION NOTES
164201300---2
A --- 1 9
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
1. Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control
wiring in separate conduit from the power wiring. The wire should be rated at 150 volts,
5 amp minimum.
2. Refer to Tables X, Y, and Z and to Chapters 2, 4, 5 and 6 of this manual for customer
interface wiring.
Table X. Customer Interface Inputs and Outputs
Ter m ina l T B 2 Name Description
1 BLDG ALARM 1
Pro
rammable UPS alarm.
cti
ated b
aremotedr
2 BLDG ALARM 1 RTN
.
contact closure.
3 BLDG ALARM 2
Pro
rammable UPS alarm.
cti
ated b
aremotedr
4 BLDG ALARM 2 RTN
.
contact closure.
5 BLDG ALARM 3
Pro
rammable UPS alarm.
cti
ated b
aremotedr
6 BLDG ALARM 3 RTN
.
contact closure.
7 BLDG ALARM 4
Pro
rammable UPS alarm.
cti
ated b
aremotedr
8 BLDG ALARM 4 RTN
.
contact closure.
Ter m ina l T B 4
1 CAN H
2 CAN L
Parallel CAN Input
3 RTN
Ter m ina l T B 5
1 Not Used
2 Not Used
3 EXTERNAL EPO
4 EXTERNAL EPO RTN
ry contact use
to act
ate remote
o
.
5 Not Used
6 RTN
Ter m ina l T B 6
1 RELAY 1 RTN
2 RELAY 1 NO
General purpose NO and NC relay contacts.
3 RELAY 1 NC
Ter m ina l T B 7
1 RELAY 2 RTN
2 RELAY 2 NO
General purpose NO and NC relay contacts.
3 RELAY 2 NC
X-Slot 4
Ter m ina l
1 UTIL_FA IL Input used to indicate utility power failure
2 ON_BYPASS Input used to indicate On Bypass status of UPS
3 BATTERY_LOW Contacts used to indicate Battery Low status of UPS