This UPS system is housed’in freestanding. double front cabinets with
safety shields behind the doors. The UPS is available in three output power
ratings, in both 50 and 60 Hz models. Smaller models may be field-upgraded to larger
output power ratings:
50 Hz Systems:
40
kVA,
32 kW maxirrium (upgradeable to 50
kVA
or 65
kVA)
50
kVA.
40 kW maximum (upgradeable to 65
kVA)
66
kVA.
52 kW maximum
60 Hz Systems:
50
kVA,
40 kW maximum (upgradeable to 65
kVA
or
80
kVA)
.65
kVA,
52 kW maximum (upgradeable to 80
kVA)
80
kVA,
84 kW maximum
The following sections detail the input, output, environmental, and battery specifications for
this UPS.
System Input
3pereUng
lnpul
Voltage
50
Hz
Models:
400
VAC for operation from
318VAC
to
455VAC
Suitable for use on
35OV,
4OOV,
and
415V systems
208 VAC for operation from 177 VAC to 229 VAC
480 VAC for operation from 400 VAC to 528 VAC
Suitable for use on 200’4
208V, and 220V systems
Dperstlng
Input
Frequency
REulge
r3
Hz of nominal
(SO
Hz or
SO
Hz)
OperaUng
Input Current
Charpe;
125%
of full load for
ovehad
+ battety charge
Actual load + 25% of full load for battery charge
Reduced
Adjustable,
set
to 102%
Input Currsd
Hsmmnic
content
Powsr
Walk-h
lO?&maximumoverzerotofullloadbasedon1O?6
THD at full load
Typically
15-20
second rectifier ramp-up to full
ulllii
load.
Power Factor
Minimum 0.g
UneSurgea
8
kV OC. 3 kA SC par ANSI 62.41 and
EC801
-4
Powerwars Plus 80 UPS Operator’s Manual
41