I
I
Environmental
t
Specifications
Operating Temperature
0 to 4O’C without derating. However, operating
at or near 40°C will adversely affect battery life
(refer to your battery specifications for more
information). The recommended operating
temperature is 25-C.
Dperatlng
Attftude
Storage
Temperature
Maximum 5000 ft.
(15OOm)
without derating
.-20
to
+70-C
(prolonged storage above 40-C
will
cause rapid battery self-discharge)
Relative
Humidity (operating and
storage)
95% maximum non-condensing
Acoustical Noise
55dSAatalmdistance
EMI
Supreasion
Meets FCC Part 15, Subpart J. for class A
devices.
42
Powemam Plus 80 UPS operator’s
h.tanual
Eleotroatatic
Discharge (ESD)
Immunity
Meets IEC
SO1
-2 specifications. Withstands up
to 25 kV without damage and
with
no
disturbance or adverse effect to the critical load.
System
Efttclency
at Full Unity
Power Factor Load and Nomlnal
Input Voltage
$0 Hz Models: Note: The 208 systems use
4OkVA-89%
an input auto
transformer
4OkVA-99%
option thet
n3dlJces
system
efficiency by 1% to
2%.
The
6oHzMode~
input isoletion bansformer
5OkVA-90%
option
mduce.s
system
65
kVA
-
91%
efficiency by
3%
90
kVA
-
91%
I
Battery Specifications
These specif~catlons are for batteries
supplll
by the UPS manufacturer, in line up and
match
caometa:
I
Banery
W
Seated, maintenancefree. high rate discharge,
-
lead acid cells
I
Nomlnal
Sattwy
String Voltage
50 Hz models: 420 VDC (210
cells)
60 Hz models: 480 VCC (240
cells)
I
float Charging
2.25 VOC
per
cell
(540 VOC based on 240 cells)
Equallzlng Charge
Sattery
Charge
Current
Umlt
rd
;rMyfjrnurn.
set to 540
VDC
at factory
Umited to 25% of full regardless of actual load
on inverter