System Output
7actttier/Charger Capaclty
)C
Flnerlng
IPS
Outpul
Capectty
htput
Voltage Regulation
lutpul
Vottege
Adjuetment
125%
Ripple
voitage
less than 0.5% peak to peak
100% current at 0.8 power factor
2% (10% to 100% load)
50 Hz Models;
400 VAC nominal adjustable from 375 VAC to
420VAC
208 VAC nominal adjustable from 196 VAC to
220 VAC
480 VAC nominal adjustable from 452 VAC to
508 VAC
>utput
Voltage Harmonk Content
3% max THO, 2% max single (for linear load)
htput
Voltage Balance
2% for 100% maximum load
imbatance
Wtput Voltage
Pheee
2’ for 100% maximum load imbalance
Xeplacement
htput
Tranalente
25%
for 100% load step or removal
3equency
Regulation
+0.005 Hz
free
running
Qnchronoua to Bypass
Sypese
within
vottage
limits of
+5%,
-8% of
output
setting;
bypass
within
+O.S
Hz
%equency Slew
Rete
hrerloed Capability
Max&m
Outpul
Cepebllfty
1 Hz per second maximum
125% for 10 minutes
150%foclOeeconde
1000%
for10cydeswtthbypase
3OO%peakfor1ocycteswithoutbypess