14 Rockwell Automation Publication 20P-TG002B-EN-P - February 2018
Chapter 2 Component Test Procedures
Save the Parameter
Configuration
It is recommended that you save the drive and communication adapter
parameter configuration before performing any service. You can save the drive
configuration in one of these ways:
Upload the drive configuration to a HIM Set
Upload the drive configuration to a DriveExecutive file (.dno)
Export the drive configuration to Connected Components Workbench
file (.iuux)
See the specific software online help for instructions on how to save or export
the drive configuration to an offline file.
Save to a HIM Set
Complete these steps to save the drive and adapter parameters to a HIM set.
1. On the HIM, access the Memory Storage menu.
2. Select the HIM CopyCat menu and press .
3. Select Device -> HIM and press .
4. Do one of the following:
If there are no existing HIM Sets, enter a name using the and
buttons to select the desired characters and press .
If there is an existing HIM Set, press to overwrite it, or select
No using the button and use the and buttons to
select the desired characters. Then press .
The HIM Set will be saved to nonvolatile memory.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 20P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 20P and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 20P Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 20P
CategoryDC Drives
LanguageEnglish

Related product manuals