Table 17 - 230V AC Input Drives
Table 18 - 460V AC Input Drives
Table 19 - 575V AC Input Drives
IMPORTANT A blank cell below a switch in Table 17, Table 18, and Table 19 indicates that
the setting is “OFF”.
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Hp DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
146 146 119 40 ON ON ON
180 180 147 50 ON ON ON ON
218 218 178 60 ON ON ON ON
265 265 217 75 ON ON ON ON
360 360 294 100 ON ON ON
434 434 355 125 ON ON ON ON
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Hp DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
167 167 136.4 100 ON ON ON ON
207 207 169.1 125 ON ON ON
250 250 204.3 150 ON ON ON ON
330 330 269.6 200 ON ON ON
412 412 336.6 250 ON ON ON ON
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Hp DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
67 67 55.1 50 ON ON ON ON
101 101 82.7 75 ON ON ON ON
135 135 110.3 100 ON ON ON ON
270 270 220.6 200 ON ON ON ON
405 405 330.9 300 ON ON ON ON