EasyManuals Logo

Rockwell Automation ArmorStart Bulletin 280G User Manual

Rockwell Automation ArmorStart Bulletin 280G
324 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #297 background imageLoading...
Page #297 background image
Safety I/O Module and TÜV Requirements F-5
Configuration of the 1732DS-IBXOBV4 Safety I/O Module and
PLC Program
The safety module must be configured as follows:
Configure the output that is connected to the I/O output cable
assembly for:
Dual (bipolar mode)
Safety Pulse Test
Configure the input that is connected to the I/O Input cable assembly
as follows:
Channel = Single
Mode = Pulsed Test Input from test output X
Source = Pulsed output from X
ArmorStart Controller - none required
Safety PLC Program – the program must:
Force the output contactors to the open state when a safety-
related stop is demanded.
Force the output contactors to remain in the open state if the SM
feedback is open after a safety-related stop is executed (see Note
1 and Note 2).
Note 1: The program must inhibit the contactor closure to satisfy safety
category 4 of 13849-1.
Note 2: The SM feedback logic should be implemented only after a safety-
related stop for the Bulletin 280/281 controllers. It should be ignored
during normal operation. One of the series contactors is used for the
normal stop/start function for these controllers. Therefore, a
malfunctioning contactor circuit cannot be distinguished from a normal
running state.
Refer to Publication SAFETY-AT018*, for programming examples.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ArmorStart Bulletin 280G and is the answer not in the manual?

Rockwell Automation ArmorStart Bulletin 280G Specifications

General IconGeneral
BrandRockwell Automation
ModelArmorStart Bulletin 280G
CategoryController
LanguageEnglish

Related product manuals