4-12 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product.
0 = 140M-D8N-C10
1 = 140M-D8N-C25
Parameter Number 22
Access Rule GET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value —
PrFlt Reset Mode
This parameter is the Protection Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number 23
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 65535
Default Value 64927
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X Short Circuit
— — — — — — — — — — — — — — X — Overload
— — — — — — — — — — — — — X — — Phase Short
— — — — — — — — — — — — X — — — Ground Fault
— — — — — — — — — — — X — — — — Stall
— — — — — — — — — — X — — — — — Control Power
— — — — — — — — — X — — — — — — IO Fault
— — — — — — — — X — — — — — — — Overtemperature
— — — — — — — X — — — — — — — — Over Current
— — — — — — X — — — — — — — — — Dnet Power Loss
— — — — — X — — — — — — — — — — Internal Comm
— — — — X — — — — — — — — — — — DC Bus Fault
— — — X — — — — — — — — — — — — EEprom
— — X — — — — — — — — — — — — — HW Fault
— X — — — — — — — — — — — — — — Restart Retries
X — — — — — — — — — — — — — — — Misc. Fault