4-12 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product.
0 = 140M-D8N-C10
1 = 140M-D8N-C25
Parameter Number 22
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value
PrFlt Reset Mode
This parameter is the Protection Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number 23
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 65535
Default Value 64927
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Short Circuit
X Overload
X Phase Short
X Ground Fault
X Stall
X Control Power
X IO Fault
X Overtemperature
X Over Current
X Dnet Power Loss
X Internal Comm
X DC Bus Fault
X EEprom
X HW Fault
X Restart Retries
X Misc. Fault

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ArmorStart Bulletin 280G and is the answer not in the manual?

Rockwell Automation ArmorStart Bulletin 280G Specifications

General IconGeneral
BrandRockwell Automation
ModelArmorStart Bulletin 280G
CategoryController
LanguageEnglish

Related product manuals