Bulletin 280G/281G Programmable Parameters 3-9
Bulletin 280G products.
Bulletin 281G products.
Produced I/O Size
This parameter reflects the
produced I/O data size in bytes.
Parameter Number 18
Access Rule GET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 8
Default Value 2
Starter COS Mask
This parameter allows the
installer to define the change-of-
state conditions that will result in
a change-of-state message
being produced
Parameter Number 19
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units
Minimum Value 0
Maximum Value 16383
Default Value
16149
16157
Bit
Function
13 12 11 10 9 8 7 6 5 4 3 2 1 0
————————————— X Tripped
———————————— X Warning
—————————— X —— Running Fwd
—————————— X ——— Running Rev
————————— X ———— Ready
———————— X ————— NET Ctl Status
——————— X —————— 140M On
—————— X ——————— Reserved
————— X ———————— Input 0
———— X ————————— Input 1
——— X —————————— Input 2
—— X ——————————— Input 3
X ———————————— Input 4
X ————————————— Input 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ArmorStart Bulletin 280G and is the answer not in the manual?

Rockwell Automation ArmorStart Bulletin 280G Specifications

General IconGeneral
BrandRockwell Automation
ModelArmorStart Bulletin 280G
CategoryController
LanguageEnglish

Related product manuals