EasyManuals Logo

Rockwell Automation ArmorStart Bulletin 280G User Manual

Rockwell Automation ArmorStart Bulletin 280G
324 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Bulletin 280G/281G Programmable Parameters 3-25
Overload Class
This parameter allows the
installer to select the overload
class
1= Overload Class 10
2= Overload Class 15
3= Overload Class 20
Parameter Number 107
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units xx.x Amps
Minimum Value 1
Maximum Value 3
Default Value 1
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number 108
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 75

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ArmorStart Bulletin 280G and is the answer not in the manual?

Rockwell Automation ArmorStart Bulletin 280G Specifications

General IconGeneral
BrandRockwell Automation
ModelArmorStart Bulletin 280G
CategoryController
LanguageEnglish

Related product manuals