Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-5
Indicates DB1 Comm Fault for Bulletin 284G.
Trip Status
This parameter provides trip identification.
Parameter Number 4
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Short Circuit
X Overload
X Phase Short
X Ground Fault
X Stall
X Control Power
X IO Fault
X Overtemperature
X Over Current
X Dnet Power Loss
X Internal Comm
X DC Bus Fault
X EEprom
X HW Fault
X Restart Retries
X Misc. Fault