Model 8712C/U/H Magnetic Flowmeter Transmitters
B-18
Series 2800 Flowtube to
Model 8712U Transmitter
Connect coil drive and electrode cables as shown in Figure B-17.
FIGURE B-17. Wiring Diagram for
Foxboro Series 2800 and Rosemount
Model 8712U
ROSEMOUNT MODEL
8712U TRANSMITTER
Electrode Connections
Coil Connections
FOXBORO SERIES 2800
FLOWTUBE
8712-8712A11A
White
Black
Any Shield
Outer Shield
White Lead
White Shield
Black Lead
Black Shield
Inner Shield
GND
L2
L1
This is a pulsed dc
magnetic flowmeter.Do
not connect ac power
to the flowtube or to
terminals1and2of
the transmitter,or
replacement of the
electronics board will
be necessary.
TABLE B-17. Foxboro Series 2800 Flowtube
Wiring Connections
Rosemount
Model 8712U
Foxboro Series 2800
Flowtubes
1L1
2L2
Chassis Ground
17 Any Shield
18 Black
19 White