Chapter 4 PAS Application Software Authorization
Branch Feeder Monitor 136_Installation Operation and Manual 40
4.3.1 Downloading Setups
You can update each setup in your BFM136 one at time or download all setups together from the site
database.
To update a particular setup, check the On-line button on the PAS toolbar, select a submeter site from the
list box on the toolbar, and then select the desired setup group from the Meter Setup menu. Click on the
tab of the setup you want to download to the device, and then click Send.
To download all setups at once, check the On-line button on the toolbar, select the submeter site from the
list box on the toolbar, and then select Download Setups from the Meter Setup menu.
Device setup settings, excluding the alarm setpoints and data log setup, are shared across all
submeters. Though you can download them to the device using any submeter address, your
changes affect all submeters in the device.
The alarm setpoints and data log setup must be downloaded separately to every submeter using its local
address. If you wish to download the same settings to all submeters in your device, prepare the alarm
setpoints and/or data log setup for one of the submeters and store them to its site database, select the
submeter site from the list box on the toolbar, and then click Download to all Submeters on the Meter
Setup menu.
4.3.2 Uploading Setups
To upload the setups from the submeter to the site database, check the On-line button on the PAS toolbar,
select the submeter site from the list box on the toolbar, and then select Upload Setups from the Meter
Setup menu.
4.4 Authorization
If communications with your device is secured, you are prompted for the password when you send new
setup data to the BFM136 .
Enter the password and click OK. If your authorization was successful, you are not prompted for the
password again until you close the dialog window.