SATEL VERSA 47
APMD-150 detector
Enter a 3-digit sequence:
1
st
digit – sensitivity of infrared path: from 1 to 4,
2
nd
digit – sensitivity of microwave path: from 1 to 8,
3
rd
digit – type of operation in the test mode: 0 (signaling violation after motion is sensed by
both detectors), 1 (signaling violation after motion is sensed by infrared detector) or 2
(signaling violation after motion is sensed by microwave detector).
For example, entering the values 4-4-0 means that the infrared sensitivity path has been set
to 4, the microwave sensitivity path also to 4, and in the test mode the detector will signal
violation (the LED will light up) after motion is sensed by both detectors.
AMD-100 and AMD-101 detectors
For detectors with electronics version 3.5 D or newer, enter the digit 0 (the lower reed switch)
or 1 (the side reed switch) to select which of the two reed switches is to be active. For
detectors with an older electronics version, no additional parameters can be programmed
(the active reed switch is selected by means of jumpers).
AGD-100 detector
Enter a digit from 1 to 3 which corresponds to the selected sensitivity for the high-frequency
channel (see: Table 8).
AVD-100 detector
For the magnetic contact (the first zone occupied by the AVD-100 detector), enter the digit 0
(the lower reed switch) or 1 (the side reed switch) to select which of the two reed switches is
to be active.
For the vibration detector (the second zone occupied by the AVD-100 detector), enter a 2-
digit sequence:
1
st
digit – sensitivity: from 1 to 8,
2
nd
digit – number of pulses: from 0 to 7.
For ex ample, entering the values 4-6 means that sensitivity has been set to 4, and the
number of pulses to 6.
ASD-100 detector
Enter a 3-digit sequence corresponding to the selected parameters, as shown in Table 9.
1st digit 2nd digit 3rd digit
digit heat detector digit acoustic signaling digit signaling time
0 disabled 0 none 1 1 minute
1 A1 1 sound type 1 2 3 minutes
2 A2 2 sound type 2 3 6 minutes
3 B 3 sound type 3 4 9 minutes
Table 9.
For example, entering the 0-2-4 means that the heat detector has been disabled, acoustic
signaling type 2 has been selected, and the signaling by means of buzzer/LEDs will last 9
minutes.
ASP-105 siren
Program the acoustic signaling parameters (the first zone to which the siren is assigned), i.e.
enter the two-digit sequence, according Table 10.