EasyManua.ls Logo

Satel VERSA Series - Wireless Expanders of Hardwired Zones and Outputs - General Rules of Programming

Satel VERSA Series
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SATEL VERSA 45
ASP-205 – both outputs to which the siren is assigned control both acoustic and optical
signaling. Parameters of the signaling triggered by each of the outputs are programmed
separately for the siren. It makes it possible to configure two different, independently
triggered ways of signaling. The outputs can thus separately control optical and acoustic
signaling or signal different types of alarm (e.g. burglary and fire). The command to trigger
signaling is sent to siren only during the response time. Hence the cut-off time for the
control panel outputs which control the siren must be longer than the response time. It is
recommended that that time correspond to the time programmed in the siren for signaling
triggered by the output.
The system zones to which the wireless sirens are assigned may be programmed as:
NC, NO or EOL – the zone will only inform about troubles related to power supply;
2EOL/NC or 2EOL/NO – the zone will inform about troubles related to power supply and
tamper.
Reaction type of the zones to which the wireless siren is assigned should be suitable for the
information to be sent:
ASP-105
first zone: low battery and tamper;
second zone: 12 V DC external power loss and tamper.
ASP-205
both zones: low battery and tamper.
Information on tamper is sent immediately, and that on troubles – during the response time.
Notes:
After starting the S
ERVICE MODE or TEST MODE and for 40 seconds after power-up,
signaling in the siren is blocked to enable installation work to be carried out. Opening the
tamper contact will not trigger any loud signaling, but information on tamper will be sent
(when in service mode, the control panel is signaling no tamper alarms). The command to
block/unblock signaling in connection with entering/exiting the test mode or service mode
is sent during the response time.
Violation of the ASP-205 siren tamper will generate a tamper alarm which will last 3
minutes (sound type 1 and optical signaling).
7.2.4 Wireless expanders of hardwired zones and outputs – general rules of
programming
The wireless expander for hardwired zones and outputs (ACX-200 or ACX-201) takes up 4
zones and 4 outputs in the system. Parameters of the expander zones and outputs are
programmed in the same way as for the other hardwired zones and outputs of control panel.
You should however remember that the sensitivity of expander zones may be different from
that programmed in the control panel:
from 20 ms to 140 ms – it corresponds to sensitivity programmed in the control panel;
over 140 ms – only some values are available: 300 ms, 500 ms, 700 ms, etc.
every 200 ms (the programmed value is rounded off to that supported by the
expander).
The expander provides on-line information about the zone status. The expander outputs are
also controlled in the on-line mode. Only the programming of zones takes place during the
response time (during one period, configuration data regarding one zone are sent to the
expander, i.e. 4 response periods are required to send information on settings of 4 zones).
Note: If communication with the controller is lost, all previously activated outputs will be
deactivated after 20 response periods.

Table of Contents

Related product manuals