WARNING
T
here is a risk of death or serious injury due to the stopping/run-down time being too
long.
b
Double the cycle time (= 16 ms) to calculate the stopping/run-down time for the
entire system.
The CPU logic execution time may increase if additional safety functions are used.
Once the logic has been configured, the final calculation for the cycle time must be
used t
o calculate the stopping time.
13.4.3 Maximum data reception interval
The maximum data reception interval is an adjustable timeout period within which valid
posit
ion data must be received.
This timeout period can be configured using the Flexi Soft Designer. For this safety sys‐
tem, the value for the maximum data reception interval is set at 8 ms. If this time is
increased, the response time will be increased too accordingly.
13 T
ECHNICAL DATA
82
O P E R A T I N G I N S T R U C T I O N S | Safe Linear Positioning 8020941/12O9/2019-08-05 | SICK