K-8
Appendix K
Trouble Message The Probable Cause Is:
MOI-1 Local Trouble This trouble is reported when the TRBL
IN input of the MOI-1/-7 is driven high.
MOI-1 Voice System Trouble This condition is caused by driving the
TRBL IN of the MOI-1/-7 high with voice
modules configured in CSG-M for this
module.
MOI-1 Zone Disarmed Output of an MOI-1/-7 (MOD-16 or
VPM-5) has been disarmed at the MXL.
MXL Network Failure The MKB/RCC-1 has lost communication
with the MNET.
Network CSGM Upload Needed A function was added to an XNET node
and had a reference to another node.
This function shall be added to each
node it references.
Network Disabled The remote PSR-1 has its MNET net-
work disabled switch set incorrectly.
Network Input Disarmed A point on another XNET node has been
disarmed.
Network Loop A Failure The Style 7 primary (A) RS485 MNET
network loop has failed.
Network Loop B Failure The Style 7 secondary (B) RS485 MNET
network loop has failed.
No CSG - Default In Use No CSG-M custom programming was
found in FLASH memory so the system
is using the default CSG-M.
Node Disconnected XNET node was logically disconnected
from the NCC.
Node Multiple Response Two nodes are programmed at the
same address.
Node Not Responding XNET wiring and/or NIM-1R module is
defective.