K-9
Appendix K
Trouble Message The Probable Cause Is:
OCC-1 Degrade Mode If this is the only problem present, the
OCC-1 module and/or OMM-1
motherboard is defective.
Out of RAM Call Pyrotronics The configuration upload is too large.
Out of Tasks Call Pyrotronics Contact the Siemens Building Tech-
nologies, Inc. Technical Services
Department.
Output Disarmed Indicates that an output point has been
manually disarmed.
PRE 1 Level AnaLASER device has reached its
PRE 2 Level pre-alarm setting.
Pre-alarm Device has reached its pre-alarm
setting.
Pre-dirty Analog Volt. Reached IEC compensation has reached a level
where the detector should be cleaned.
Printer Off Line/Fault A supervised printer is not responding.
Printer Out Of Paper The TSP-40 has run out of paper.
PSR-1 Driver Disarmed A PSR-1 relay output device has been
disarmed.
Relay Coil Open The relay coil at this address is open.
Relay Disarmed The relay at this address has been
disarmed from the Control menu.
Relay Driver Inoperative The relay on the CRM-4 or CSM-4 at
this address does not operate when
commanded to energize.
Relay Supervision Failure The relay at this address has a coil
failure.
Remote Node Disconnected XNET node was logically disconnected
from the NCC.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals