EasyManua.ls Logo

Siemens LMV36.520A1 - Page 100

Siemens LMV36.520A1
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 9 Selection of operating mode 25.09.2013
No. Parameter
301
Fuel 1: Burner operating mode (fuel train, modulating / multistage, actuators,
etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = HO mod with circulation
¹)
24 = HO 2-stage with circulation
¹)
25 = HO mod without circulation control
¹)
26 = HO 2-stage without circulation control
¹)
27 = HO 3-stage without circulation control
¹)
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0

Table of Contents

Related product manuals