23.6.2 Restore
Parameter 000: flashes.
Display: Parameter 000: flashes, Int does not.
/
reset
Only
OEM
level
Press
/
reset
to go to parameter group 041.
Display: Parameter 041: flashes, ._._ does not.
Press to select parameter 050
Display: Parameter 050. flashes, index 00: and value 0 do
not.
/
reset
7548z358/1009
Press
/
reset
to go to parameter bAC_UP
Display: Parameter bAC_UP
7548 z 359/ 1009
Press to select parameter rEStorE
Display: Parameter rEStorE
/
reset
Press
/
reset
to select the restore process.
Display: Value 0
Press
to shift the value in change mode 1 position to
the left.
Display: Value 1 flashes.
Note
To detect potential display errors, the value is displayed 1
place shifted to the left.