Value Error  Remedy 
-22  Air actuator not referenced 
Air actuator is not referenced or has lost its reference.
1. Check if the reference position can be approached. 
2. Check if actuators have been mixed up. 
3. If error only occurs after the start of standardization,  
    the actuator might be overloaded and cannot reach its 
    destination. 
-23 VSD deactivated 
Standardization was started with VSD deactivated 
 activate the VSD and repeat standardization 
-24  No valid operation mode 
Standardization was started without valid operation 
mode 
 activate valid operation mode and repeat  
     standardization 
-25  Pneumatic air-fuel ratio control 
Standardization was started with pneumatic air-fuel ratio 
control  
→ standardization with pneumatic air-fuel ratio control is 
    not possible 
-128 
Running command with no preceding 
standardization 
VSD is controlled but not standardized  
 make standardization 
-255  No standardized speed available 
Motor turns but is not standardized  
 make standardization 
 
The result of speed standardization (100% speed) can be read out via parameter. The 
speeds acquired by the 2 microcontrollers can differ by about 1.5%, the reason being 
slightly different resonator frequencies. 
 
No.  Parameter
642.0 Standardized speed 
Index 0 = speed 1 
642.1 Standardized speed 
Index 1= speed 2 (internal monitoring) 
 
13.12 Control of fan motor with pneumatic fuel-air 
ratio control
  
 
If control of the fan motor is employed for burners with pneumatic air-fuel ratio control, 
only the control path is used. There is no need to connect a speed feedback signal and 
to have speed control (for operating modes, refer to chapter Selection of operating 
mode).