36/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 4 Technical data 25.09.2013
4.5 Switch unit AGM60...
Mains voltage AC 120 V -15% / +10%
Mains frequency 50/60 Hz ±6%
Power consumption <5 W (typically) (without actuator supply)
Safety class I with parts according to II and III to
DIN EN 60730-1
Galvanic separation between mains
voltage terminals and actuator signal
lines and actuator supply lines
No
Degree of protection IP00
Note:
The burner or boiler manufacturer (OEM)
must ensure degree of protection IP40 to
DIN EN 60529 for burner controls by
adequate installation of the AGM60...
The AGM60... together with the LMV36...
is suited for installation under the burner
hood or inside a control cabinet or control
panel
Detection time fuel changeover <400 ms
Switching frequency fuel changeover Min. 3 s
Switching cycles fuel changeover Max. 5´000
Perm. mains primary fuse (externally) Max. 6.3 AT
Power must always be supplied via the
basic unit
(refer to chapter Inputs / Outputs)
Mains supply:
Input current depending on the operating state of the unit
Mains voltage is monitored by the burner control
Dimensions (W x H x D) 180.7 x 120.7 x 51.7 mm
Mounting Top hat rail to DIN EN 60715,
35 mm or screwed