Building Technologies Division  Basic documentation LMV36...  CC1P7544en 
Infrastructure & Citiies Sector  9 Selection of operating mode  25.09.2013 
Operating mode 
parameter 201 / 
301 
Fuel train 
Fuel-air ratio 
control 
Fuel actuator 
Air actuator 
Feedback signal 
VSD 
Description 
26  HO o. Umsp 
2-stage 
¹) 
2-stage  
●  ● 
Heavy oil direct ignition without circulation control, electronic 2-stage 
ratio control. Optional with VSD with speed feedback signal 
27  HO o. Umsp 
3-stage 
¹) 
3-stage  
●  ● 
Heavy oil direct ignition without circulation control, electronic 3-stage 
ratio control. Optional with VSD with speed feedback signal 
 
(Also refer to chapter Fuel trains) 
 
¹) Selected operating mode is not released for the basic unit.  
    With select: Error code 210 diagnostic code 0 
 
The VSD can be used with any of the operating modes (refer to chapter VSD). 
 
No. Parameter 
542 
Activation of VSD / PWM fan 
0 = inactive 
1 = active
 
 
Note 
For configuration of the analog output when the VSD is activated, refer to 
chapter Load output X74 pin 3! 
 
9.1 Deleting curves 
 
To delete curves, the operating mode must be set to undefined «--». In that case, only 
the fuel curves are deleted, the direction of rotation or the reference position of the 
actuators is not changed.