Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 20 Error history 25.09.2013
20 Error history
The LMV36... system provides an error history in which the last 25 errors are stored.
The first entry represents the current error state and can also be error-free, refer to Error
code list.
Error
code
Diagnostic
code
Meaning for the LMV36... system
200 OFF # System error-free
20.1 Error classes
The errors are subdivided into error classes, depending on the severity of the switch-off
response. The current error shows all classes. Only the errors of the most important
classes are included in the history.
Error class Priority Meaning History
0 Highest Lockout
1 Safety shutdown with software reset
2 Undervoltage
3 Safety shutdown: Safety phase
4 Safety shutdown: Start prevention
5 Safety shutdown: Shutdown
6 Lowest Message without shutdown response