Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 13 Fan control 25.09.2013
13.13 EMC of LMV36... and VSD
The function and EMC tests with the LMV36... system have been successfully
conducted in connection with the following makes and types of VSDs:
Siemens: SED2-0.37 / 22 X
Danfoss: VT2807
During operation, VSDs generate electromagnetic interference on the mains network.
For this reason, the supplier’s specifications must be strictly observed to ensure that
makeup of the system is in compliance with EMC regulations:
Siemens: Operating Instructions installation conforming to EMC
Danfoss: Technical Brochure radio suppression filter
Data Sheet on Danfoss EMC filter for long motor cables
Caution!
When using other types of VSD, compliance with EMC regulations and trouble-
free operation are not ensured!