8.3 Connecting cable between AGM60... and
LMV36... basic unit (AGV61.100 cable)
This cable is required when, due to the selected type of fuel train (refer to chapter
Selection of operating mode), 2 fuel actuators are needed.
For that, the 2 fuel actuators must be connected to terminals X54a and X54b of the
AGM60... The AGV61.100 cable is required for making the electrical connection
between the 2 fuel actuators and the basic unit.
If only 1 fuel actuator is used, it must be connected directly to the basic unit.
Connection plug assignment of cable:
1 = pink or alternatively red
2 = white or alternatively black
3 = brown
4 = grey
5 = yellow
6 = green