Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
P
Vhmins%
Bild 94/0707
When symbol or is no longer highlighted, you can
press ESC a second time.
ESC
P
Vh
mi n
s%
Bild 128/0707
The warm settings for fuel-air ratio control by the LMV36... are now completed.
28.11.5 Warm settings for modulating mode («G mod pneu», «Gp1 mod pneu»
and «Gp2 mod pneu»)
Note
Refer to chapter Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)! Here, only the air requires adjustment with
A
.
28.11.6 Cold settings for «G mod», «Gp1 mod», «Gp2 mod» and «Lo mod»
Note
Refer to chapter Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)!
With no flame, however, no actuator travel and no automatic operation after the settings have
been made.
28.11.7 Cold settings for «G mod pneu», «Gp1 mod pneu» and «Gp2 mod
pneu»
Note
Refer to chapter Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)!
With no flame, however, no actuator travel and no automatic operation after the settings have
been made. Here, only the air requires adjustment with
A
.