204/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
28.11.8 Interpolation of curvepoints
Note
Changing a curvepoint in the cold position requires a new approach to all
curvepoints in the warm position to verify the change on the burner itself. After
changing the curvepoint, the normal display of the AZL2... shows OFF UPr0 / OFF
UPr1.
To the next curvepoint
or
to select the curvepoint
P
Vh
mi n
s%
Bild 129/0707
The selected curvepoint is displayed.
F
P
Vh
mi n
s%
Bild 130/0707
Keep
F
depressed.
The fuel actuator has been selected for
changing.
F
and
or
P
Vh
mi n
s%
Bild 131/0707
Keep
F
depressed and press or to
adjust the fuel actuator.
In the case of warm settings, the actuator
follows directly the adjustments made.
The changes are saved.
P
Vh
mi n
s%
Bild 132/0707
After releasing
F
, the point is selected
again.
A
P
Vh
mi n
s%
Bild 133/0707
Keep
depressed.
The air actuator has been selected for editing.
A
and
or
P
Vh
mi n
s%
Bild 134/0707
Keep
depressed and press or to
adjust the air actuator.
In the case of warm settings, the actuator
follows directly the adjustments made.
The changes are saved.
P
Vh
mi n
s%
Bild 135/0707
After releasing
, the point is selected
again.
To the next curvepoint
Back to the previous
curvepoint