38/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 4 Technical data 25.09.2013
4.5.3 Cable lengths
Mains line
LMV36... AGM60...
Max. 3 m (100 pF/m)
Fuel valves Max. 3 m (100 pF/m)
Other lines Max. 3 m (100 pF/m)
Fuel selector Max. 20 m (100 pF/m)
Load controller LR Max. 20 m (100 pF/m)
Specification as per EN 60730-1
Type of shutdown or interruption of each circuit
Shutdown with microswitch
Single-pole
Mode of operation
Type 2 B
4.5.4 Cross-sectional areas
The cross-sectional areas of the power supply lines (L, N and PE) must be capable of
carrying the rated currents according to the built-in unit fuse of the respective basic unit
(max. 6.3 AT).
Min. cross-sectional area 0.75 mm²
(single- or multi-core to VDE 0100)
Cable insulations must satisfy the relevant temperature requirements and environmental
conditions.
4.5.5 Electrical connections of actuators
The ready connected actuator cables must not be extended.
4.5.6 Environmental conditions
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -30...+60 °C
Humidity <95% r.h.
Operation
DIN EN 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60 °C
Humidity <95% r.h.
Caution!
Condensation, formation of ice and ingress of water are not permitted!