Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 11 Electronic fuel-air ratio control 25.09.2013
11.3.5 Limitation of modulation range
If the modulation range shall be further restricted from 20 to 100% against the defined
curve, 4 parameters are available to define a new low-fire and high-fire position.
No. Parameter
545
Lower output limit
undefined = 20 %
565
Fuel 1: Lower output limit
undefined = 20 %
546 Upper output limit
undefined = 100 %
566 Fuel 1: Upper output limit
undefined = 100 %
20 % Low-fire
Lower output
limit P545
Upper output
limit P546
100 % High-fire
VSD
Figure 75: Restriction of modulation range